CL200UBCT - Boardman Transformers - CL Range

CL200UBCThttps://www.cca.co.uk/image.php?filename=cl200ubct.jpg&stockcode=CL200UBCT&category=000700490002&width=1000&height=1000

CL200UBCT - Boardman Transformers - CL Range - 200VA Control Circuit Transformer - 240/24 - Centre Tapped

For high-standard control transformers, choose Boardman Transformers. These reliable industrial control transformers comply with the high safety standards this industry has come to expect. These industrial control transformers will tep down the voltage to power the control devices of a circuit or machine. The reduced voltage provides a much safer environment for technicians working on the equipment. 

Boardman Transformer Range: CL 

Control Transformer:  Class 1 Isolation Transformer with Earth Screen between Primary

and Secondary

Standard: IEC / BS-EN 61558

Rating: 200VA

Voltage in: 240V

Voltage out: 24V 


Not the right transformer? 

To choose the size of transformer required for an application the total inrush VA must be calculated. This figure is then applied to the table above with the maximum allowable voltage drop taken into account. For example, for a calculated inrush of 2,100VA the appropriate transformer is as follows:

  • For 10% drop in output volts during inrush, choose 750 VA

  • For 5% drop in output volts during inrush, choose 1000 VA

Consideration must also be given to the continuous VA requirement.


If you need additional assistance on choosing the right transformer for your application, contact your local CCA branch. 

GBP
Stock Code: CL200UBCT
17 In Stock for despatch
60.32£50.27 (exc VAT) per 1
£60.32 (inc VAT)
Quantity: - +

CL200UBCT - Boardman Transformers - CL Range - 200VA Control Circuit Transformer - 240/24 - Centre Tapped

For high-standard control transformers, choose Boardman Transformers. These reliable industrial control transformers comply with the high safety standards this industry has come to expect. These industrial control transformers will tep down the voltage to power the control devices of a circuit or machine. The reduced voltage provides a much safer environment for technicians working on the equipment. 

Boardman Transformer Range: CL 

Control Transformer:  Class 1 Isolation Transformer with Earth Screen between Primary

and Secondary

Standard: IEC / BS-EN 61558

Rating: 200VA

Voltage in: 240V

Voltage out: 24V 


Not the right transformer? 

To choose the size of transformer required for an application the total inrush VA must be calculated. This figure is then applied to the table above with the maximum allowable voltage drop taken into account. For example, for a calculated inrush of 2,100VA the appropriate transformer is as follows:

  • For 10% drop in output volts during inrush, choose 750 VA

  • For 5% drop in output volts during inrush, choose 1000 VA

Consideration must also be given to the continuous VA requirement.


If you need additional assistance on choosing the right transformer for your application, contact your local CCA branch. 

Weight2.8kg
Width96mm
Height102mm
Depth86mm

Click on any of the following links to download the file.