The CL1 range of control transformers from Boardman Transformers is made using an automated winding and welding machine giving them a high-quality finish. Designed to comply with the IEC61558 Safety Standards, these control circuit transformers will reduce supply voltages to control circuits so that your application can work safely.
Boardman Transformer Range: CL Control Transformer: Class 1 Isolation Transformer with Earth Screen between Primary and Secondary Standard: IEC / BS-EN 61558 Rating: 100VA Voltage in: 240V Voltage out: 24V
Not the right transformer? To choose the size of transformer required for an application the total inrush VA must be calculated. This figure is then applied to the table above with the maximum allowable voltage drop taken into account. For example, for a calculated inrush of 2,100VA the appropriate transformer is as follows:
For 10% drop in output volts during inrush, choose 750 VA For 5% drop in output volts during inrush, choose 1000 VA
Consideration must also be given to the continuous VA requirement.
If you need additional assistance on choosing the right transformer for your application, contact your local CCA branch.
CL100UBCT - Boardman Transformers - CL Range - 100VA Control Circuit Transformer - 240/24 CT
The CL1 range of control transformers from Boardman Transformers is made using an automated winding and welding machine giving them a high-quality finish. Designed to comply with the IEC61558 Safety Standards, these control circuit transformers will reduce supply voltages to control circuits so that your application can work safely.
Boardman Transformer Range: CL Control Transformer: Class 1 Isolation Transformer with Earth Screen between Primary and Secondary Standard: IEC / BS-EN 61558 Rating: 100VA Voltage in: 240V Voltage out: 24V
Not the right transformer? To choose the size of transformer required for an application the total inrush VA must be calculated. This figure is then applied to the table above with the maximum allowable voltage drop taken into account. For example, for a calculated inrush of 2,100VA the appropriate transformer is as follows:
For 10% drop in output volts during inrush, choose 750 VA For 5% drop in output volts during inrush, choose 1000 VA
Consideration must also be given to the continuous VA requirement.
If you need additional assistance on choosing the right transformer for your application, contact your local CCA branch.